Design and costing of a Harmonic Filter.
Mr. Sachin V. Shelar. ( R & D Engineer )
Madhav Capacitors Pvt. Ltd., Pune.
A harmonic filter essentially consists of a power capacitor, a tuning reactor and its control gear. It will act in parallel with an untuned basic power factor improvement capacitor bank.
For the designing purpose we require some data such as load details, existing power factor, required new power factor, total harmonic distortion, individual harmonic details etc. This data can be obtained from a harmonic analyser.
First calculate the total KVAR required to improve the power factor to the desired value. Then distribute the total KVAR into two parts, a normal capacitor bank (untuned) for power factor correction and a filter bank (tuned) for filtration purpose. This is explained in detail in the example given below.
We consider a practical example of a rolling mill, circuit diagram is as shown in Fig. 1.

Fig.1 Line diagram of the load.
Data obtained from harmonic analyser at 30% load :
Load in KW = 606.20.
Power factor = 0.42 lag.
ITHD = 30.47.
5th harmonic current = 39.25 Amp.
Assuming required power factor to be 0.97, we calculate the total KVAR required to raise the power factor from 0.42 to 0.97.
KVAR required = KW (tanf 1- tanf 2)
KW = 606.20
Cosf
1 = 0.42
tanf 1
= 2.16
Cosf
2 = 0.97
tanf 2
= 0.25
KVAR required = 606.20 (2.16 - 0.25)
= 1157.80 KVAR.
1158 KVAR.
Thus we require 1158 KVAR to raise the power factor to 0.97.
From the readings it can be seen that, ITHD is 30.47 but maximum harmonic current distortion as recommended by IEEE specifications C-519-1992 is 4.0.
Out of 1158 KVAR to be installed we employ 30% KVAR towards filter duty and remaining KVAR for power factor correction.
Thus,
Filter KVAR = 30% of 1158.
= 347.4 KVAR.
Filter KVAR
350 KVAR.
Design of filter :
The basic diagram is as shown in Fig. 2.

Fig. 2 - Basic circuit diagram.
We consider a star connected capacitor bank.
![]()

C = 9.21 mfd/Ph.
![]()
![]()
XC50 = 345.80 W /Ph.
![]()
XC250 = 69.16 W /Ph.
For resonance at 5th harmonic we should have,
XL250 = XC250.
XL250 = 69.16 W /Ph.
From above we can write,
XL50 = 13.82 W /Ph.
So,
![]()

L = 44 mH.
![]()
IC50 = 18.37 Amp.
5th harmonic current from the data is ,
I250 = 39.25 Amp.
40 Amp
![]()
IRMS = 44 Amp.

Fig. 3 Parameters.
Voltage across reactor,
VL = VL50 + VL250
VL50 = Voltage drop across reactor due to fundamental
current.
= I50 x XL50
= 18.37 x 13.82
VL50 = 253.87 V.
VL250 = Voltage drop across reactor due to 5th harmonic
current.
= I250 x XL250
= 40 x 69.16
VL250 = 2766.4 V.
Total voltage across reactor (VL) :
VL = VL50 + VL250
= 253.87 + 2766.40
= 3020.27
VL
3020 V.
KVAR rating of single phase reactor :
= VL x IRMS
= 3020 x 44.
= 132.88 KVAR/Ph.
133 KVAR.
We use 3 such reactors.
Voltage across capacitor,
VC = VC50 + VC250
VC50 = Phase voltage
=
= 6350 V.
VC250 = I250 x XC250 = 40 X 69.16.
= 2766.4 V.
VC250
2766 V.
Total voltage across capacitor (VC) :
VC = VC50 + VC250
= 6350 + 2766
VC = 9116 V.
KVAR rating of capacitor :
= VC x IRMS
= 9116 x 44.
= 401.10KVAR/Ph.
401 KVAR.
Costing :

Without filter bank circuit diagram.
|
Sr. No. |
Item |
Quantity |
Cost in Rs. |
|
1 |
11 kV Outdoor VCB. |
1 No. |
2,10,000 |
|
2 |
Breaker panel. |
1 No. |
1,80,000 |
|
3 |
3 Phase isolator |
1 No. |
26,000 |
|
4 |
2.3 KVAR, Gap cored series reactor. |
1 No. |
1,00,000 |
|
5 |
1158 KVAR capacitor bank including structure and fuses |
1 No. |
1,70,000 |
|
Total = |
6,86,000 |
||
2. Capacitor bank with filter :

With filter bank circuit diagram.
|
Sr. No. |
Item |
Quantity |
Cost in Rs. |
|
1 |
11 kV Outdoor VCB. |
1 No. |
2,10,000 |
|
2 |
Breaker panel. |
1 No. |
1,80,000 |
|
3 |
3 Phase isolator. |
2 No. |
52,000 |
|
4 |
1.6 KVAR, Gap cored series reactor. |
1 No. |
85,000 |
|
5 |
808 KVAR main capacitor bank. |
1 No. |
1,16,000 |
|
6 |
399 KVAR tuning reactor. |
1 No. |
5,05,000 |
|
7 |
1203 KVAR capacitor. (Harmonic filter) |
1 No. |
2,18,000 |
|
Total = |
13,66,000 |
||
Conclusion :
When normal power factor correction bank is converted into the filter bank the cost almost becomes twice, but with a load of 2000 KW and 40 amp of 5th harmonic current at 11 kV it can be justified.
This particular consumer has been trying to maintain his power factor near 0.85 by -
He burns and replaces his LT capacitors within 2-3 months and then pays a heavy penalty until a new set of capacitor is installed.
Rs. 4,20,000/-, which includes cost of switchgear, cables, installation etc.
His monthly electricity bill is Rs. 10,60,000/-. His penalty will come to Rs. 1,06,000/- per month.
Reference :