TESTING PLAN |
||
|
Following tests are offered on our panels |
||
|
|
Insulation Resistance test with a 500 Volts megger. Control transformers: meters and relay coils(230 V) and relays will be disconnected during this test and the next one. |
|
|
|
An A.C. withstand test for 2 KV A.C. for one minute will be carried out. |
|
|
|
Operational tests both in manual mode and automatic mode will be carried out.
|
|
|
Manual mode |
All stations will be switched on consecutively or at random. They will be switched off and switched on again. There will be a delay of one minute or more between switching off and re switching. |
|
|
Automatic mode |
There will be consecutive switching on or off only. In this mode the push buttons will be non-operative. In this mode there will be a delay of 1 minute or more between successive operations in either direction.
|
|
![]()
|