CONSTRUCTION |
||
|
|
Housing |
|
|
|
Thickness of sheets used = 14 SWG or 2 mm. Thickness of base channel or structural = 3 mm min
|
|
|
Components |
||
These will be of heavy duty (as per IS-4047) quick-make, quick-break type.
All L.T. Fuses will have an ISI Mark. They will be mounted on fuse bases. They will be easily approachable.
Anti condensation space heaters metal enclosed, low surface temperature, suitable for 240 V,1 phase supply along with a switch and fuse will be provided in each panel. Item 2,3 and 4 will be suitably derated for continuous capacitor duty. The makes of all the above items will be L& T or Siemens (Other makes will be provided when specified). |
||
|
Wiring |
||
Minimum size of control wiring will be in 1.5 Sq. mm2.(2.5 sq. mm will be provided when specified).Identification ferrules will be provided for all wires at each connection point as per IS-5578-Dependent, local and marking.
|
||
|
Earthing |
||
|
Sheet metal panels-on which live parts are mounted. Including doors and capacitors when enclosed in a panel, will be firmly connected into two separate earthing points brought out at two convenient locations on the outside of the panel. The earthing may be achieved through one of the followings:- Capacitors Assemblies and Door through distinct copper links (bare). Other sheet metal parts-through continuity in welding: tapped and unpainted holes with bolting connections: optionally through copper wires. Minimum copper conductor size will be 6 Sq. mm. There will be two such conductors per specified member. |
||
|
Hardware |
||
|
All the M.S. Hardware will be electro-galvanised and passivated. Brass hardware will not be plated to distinguish it from plated M.S.Hardware. |
||
|
Painting |
||
|
All metal parts will be thoroughly cleaned degreased and given the following coats: One coat of cold phosphetising Two coats of primer Two coats of enamel paint in specified shade (Dove Gray) (Epoxy Based or other types of painting will be provided when specified.) |
||
|
Name-plates |
||
|
Each panel will have it's main name plate as per drawing. Each push button station will have a label indicating capacitor bank no, which it controls. The earthing points will have earthing stickers. Inside the panel, each contactor station will have a capacitor bank no. Label indicating the bank it controls. The Labels will be in aluminium plate suitably etched and painted. (Any other type of label or any extra labels will be provided when specified). |
||
![]()